Description
The Schneider Electric Modicon TM3 I/O modules expand the local or distributed I/O capacity of Modicon M221, M241, M251, M262, and M340 (via TM5 coupler) PLC/PAC systems. They snap onto the right side of the controller (local expansion) or onto a TM5 / TM3 bus coupler for remote I/O. Listed models include:
- TM3DQ16R → 16-point Digital Output, Relay (NO), 24V DC / 250V AC, 2A per point.
- TM3DI32K → 32-point Digital Input, 24V DC sink/source (positive/negative logic).
- TM3DQ32UK / TM3DQ32TK → 32-point Digital Output, Transistor (NPN/PNP — UK=source PNP; TK=sink NPN).
- TM3AI8 → 8-channel Analog Input (Voltage/Current/TC/RTD — universal per channel).
- TM3TI4 → 4-channel Thermocouple / RTD Temperature Input.
- TM3AQ2 → 2-channel Analog Output (±10V or 0/4–20mA).
All TM3 modules share hot-swap capability (on supported CPUs), diagnostic LEDs per channel/group, and automatic detection by the SoMachine / EcoStruxure Machine Expert software.
Key Features
- Local / Remote Expansion: Snap to M221/M241/M251/M262 or to TM5 bus coupler.
- Auto-Detect: Recognized automatically in programming software — no manual addressing (local); DIP-switch or software addressed (remote).
- Diagnostics: Per-channel status LEDs + module-level error LED.
- Hot-Swap: Supported on M241/M251/M262 with proper configuration.
- Country of Origin: France / China (Schneider global)
Model & Specification Table
Model | Type | Channels | Key Spec | Typical Use |
|---|---|---|---|---|
TM3DQ16R | Digital Output | 16 DO | Relay NO, 24V DC/250V AC, 2A/pt | AC/DC load switching (solenoids, contactors, lamps) |
TM3DI32K | Digital Input | 32 DI | 24V DC sink/source, 4ms filter | High-density DI for sensors, switches |
TM3DQ32UK | Digital Output | 32 DO | Transistor PNP (Source), 0.5A/pt | Fast DC load / servo enable / stepper pulse |
TM3DQ32TK | Digital Output | 32 DO | Transistor NPN (Sink), 0.5A/pt | NPN sink-type DC loads |
TM3AI8 | Analog Input | 8 AI | Uni. V/I/TC/RTD (16-bit) | Process & temp. meas. |
TM3TI4 | Temp. Input | 4 TI | Thermocouple / RTD only (high-res) | Furnace/kettle temp. mon. |
TM3AQ2 | Analog Output | 2 AO | ±10V or 0/4–20mA (12/16-bit) | Valve pos., setpoint to drive |
⚠️ Important Notes:
Relay vs Transistor: TM3DQ16R = relay (good for AC loads / mixed DC-AC; slower, mechanical life ~100k ops @ rated load). TM3DQ32U/T = transistor (fast, long life, DC only, observe PNP/NPN wiring). TM3DI32K: 32 inputs share common(s) — verify sinking (0V common) vs sourcing (24V common) wiring per your sensor type. Maximum Expansion: Local bus on M221/M241 typically supports up to 7 TM3 modules (check CPU manualfor exact limit); remote via coupler supports more. 5V Backplane Current: High-density modules (32-ch) draw more 5V from CPU backplane — verify CPU’s total available backplane current.
Technical Specifications (Representative — TM3DQ16R & TM3AI8)
TM3DQ16R — 16-pt Relay Output
Parameter | Value |
|---|---|
Outputs | 16 × NO Relay (form A) |
Rated Load Voltage | 5…30V DC / 5…250V AC |
Max. Switching Current | 2 A / point (resistive); 5 A / common (sum of grouped pts) |
Mechanical Life | 10⁷ ops (no load); 10⁵ ops @ rated resistive load |
Response Time (ON/OFF) | ≤ 10 ms / ≤ 15 ms (typical) |
Isolation | 1500 V AC (I/O to logic) |
Dimensions (W×H×D) | 40 mm × 90 mm × 70 mm |
Weight | ~ 0.12 kg |
TM3AI8 — 8-ch Universal Analog Input
Parameter | Value |
|---|---|
Inputs | 8 × Universal (±10V, 0–10V, 0/4–20mA, RTD, TC) |
Resolution | 16-bit + sign |
Conversion Time | ~ 5 ms / channel (typ.) |
Input Impedance | > 1 MΩ (V), 250 Ω (I) |
Wire Break Detection | Yes (current mode & 3/4-wire RTD) |
Dimensions | 40 mm × 90 mm × 70 mm |
Warranty & After-Sales
- Factory new units: 12 months warranty
- Refurbished units: 3-6 months warranty
- Technical support for:
- TM3 addressing (auto on local bus; DIP/software for remote)
- Wiring diagrams (PNP vs NPN transistor output; sinking vs sourcing DI)
- Analog input range & filtering configuration in EcoStruxure Machine Expert / SoMachine
- Backplane current budget check vs. CPU spec
- Cross-reference vs. TM2 (older Twido) modules — TM3 NOT backward compatible with Twido base
Delivery Time
- Standard delivery: 3-5 working days (stock items)
- Express shipping available upon request
Why Choose Our Store
- Genuine Schneider Electric Modicon TM3 components
- Global supply network with competitive pricing
- Expertise in Modicon M221/M241/M251/M262 local & remote I/O expansion
- Comprehensive technical documentation (datasheets, GSD files, SoMachine examples)
- Responsive customer service and support
Applications
- Machine-level I/O for packaging, converting, material handling (M241/M262 + TM3)
- High-density DI/DO for conveyor / palletizer control (TM3DI32K / TM3DQ32U)
- Process signal acquisition (TM3AI8 + TM3AQ2 for simple loops)
- Temperature monitoring (TM3TI4 for kiln/oven)
- Retrofit from Twido (TM2) to M221 + TM3 for modernized machines





Reviews