Schneider Electric Harmony RM22LA32MR / RM4LA32B / RM4LA32F / RM4LA32M / RM4LA32MW — Liquid Level Control & Monitoring Relays

Schneider Electric Harmony RM22LA32MR / RM4LA32B / RM4LA32F / RM4LA32M / RM4LA32MW — Liquid Level Control & Monitoring Relays | Shop On Ebay

Factory New Parts : Warranty 12 Months​
Refurbished Units : Warranty 3–6 Months​
Tested & Certified | Ships Worldwide​
Technical / Configuration Support Available​
Warranty Extension and Urgent Delivery supported. Get your quote or lead time now !

Description

The Schneider Electric Harmony RM22-LA / RM4-LA series​ are specialized liquid level control and monitoring relays, designed to work with conductive (resistive) level electrodes (probes) for automatic pumping control (fill / empty mode) and level alarm functions in tanks, sumps, and wells.
  • RM22LA32MR​ → 2-electrode level controller with pump protection​ (detects dry-run, overfill; DIN-rail mount, 24V AC/DC or 230V AC coil variants — check suffix).
  • RM4LA32B / RM4LA32F / RM4LA32M / RM4LA32MW​ → Level monitoring relays​ from the older RM4 family — provide adjustable sensitivity, delay, and mode (pump-up / pump-down / alarm only) with 2 or 3 electrode inputs and optional fault relay.
These units pass a low AC sensing current through the liquid — when probes are bridged by conductive liquid, the relay changes state according to the selected mode (Empty = pump fills until upper probe touched; Fill = pump empties until lower probe uncovered). They include sensitivity adjustment (0.5–100 kΩ typical)​ to compensate for scaling / water conductivity changes and timed delay​ to prevent chattering from wave action.

Key Features

  • Electrode Inputs: 2 or 3 conductive probes (common REF + HIGH + LOW or ALARM probe).
  • Modes: Pump-Down (empty tank), Pump-Up (fill tank), Alarm-Only.
  • Sensitivity: Adjustable 0.5–100 kΩ (compensates for probe fouling / low conductivity).
  • Time Delay: 0.1–10 s (typical) to reject wave-induced cycling.
  • Supply Voltages: 24V AC/DC, 110V AC, 230V AC — confirm exact suffix.
  • Output: 1 or 2 changeover contacts (NO/NC) — pump command + alarm.
  • Country of Origin: France / Italy (Schneider Global)

Model Reference Table

Model
Series
Function
Electrode Inputs
Typical Supply
Notes
RM22LA32MR
RM22 (Harmony)
Level Controller + Pump Protection
2–3 probes (REF/L/H or REF/L+Alarm)
24V AC/DC or 230V AC check suffix
Modern compact DIN version
RM4LA32B
RM4 (Legacy)
Level Monitor / Controller
2 probes (REF+L/H selectable)
230V AC (typical)
Older gen., still widely used
RM4LA32F
RM4 (Legacy)
Level Monitor — Fill Mode pref.
2–3 probes
230V AC
Fill (pump-up) bias
RM4LA32M
RM4 (Legacy)
Level Monitor — Empty Mode pref.
2–3 probes
230V AC
Empty (pump-down) bias
RM4LA32MW
RM4 (Legacy)
Level Monitor with wider adj.
2–3 probes
230V AC (some 24V)
Multi-voltage / wide range
⚠️ Installation Warnings:
  1. Probe Voltage is LIVE!​ The sensing voltage on probe terminals is low-current AC — treat as live.
  2. Use Proper Electrodes: Only use conductive-type level electrodes (stainless steel rods with insulation). Not for capacitive/ultrasonic floats.
  3. Sensitivity Setting: Start with midpoint; adjust so relay reliably picks/drops with liquid present/absent — too-high sensitivity causes false triggering from moisture/condensation on probe stems.
  4. Pump Protection (RM22LA32MR): Configure dry-run delay & overfill lockout per tank geometry.

Technical Specifications (Representative — RM22LA32MR)

Parameter
Specification
Model
RM22LA32MR (Schneider Electric Harmony RM22-LA)
Function
Conductive liquid level control — Pump-Up / Pump-Down / Alarm
Number of Electrodes
2 (REF + Level) or 3 (REF + Low + High) depending on mode
Sensitivity Range
0.5 – 100 kΩ (adjustable potentiometer)
Time Delay
0.1 – 10 s (adjustable — suppresses wave chatter)
Supply Voltage
Check suffix: commonly 230V AC 50/60Hz or 24V AC/DC
Output Relay
1 or 2 × Changeover (CO / Form C), 5 A @ 250V AC (resistive)
Pump Protection
Dry-run detection & overfill lockout (on RM22LA32MR)
Mounting
35 mm DIN rail (EN 60715)
Dimensions (W×H×D)
36 mm (2 TE) × 90 mm × 72 mm (typical for RM22)
Weight
~ 0.15 kg
Standards
IEC 60255, CE, UL, CSA, RoHS

Warranty & After-Sales

  • Factory new units: 12 months warranty
  • Refurbished units: 3–6 months warranty
  • Technical support for:
    • Mode selection (Pump-Up vs Pump-Down wiring & probe placement)
    • Sensitivity & delay adjustment for turbulent/foaming liquids
    • Probe layout recommendation (reference probe always submerged; Hi/Lo probes at setpoints)
    • Cross-reference to obsolete Zelio level relays / older RM4 replacements
  • Wiring diagram provided (terminal IDs: A1/A2 = supply; 11-12-14 = output; S1/S2/S3/S4 = electrode commons & probes)

Delivery Time

  • Standard delivery: 3–5 working days (stock items)
  • Express shipping available upon request

Why Choose Our Store

  • Genuine Schneider Electric Harmony control relays
  • Global supply network with competitive pricing
  • Expertise in pump control panels, sump/borehole level switching & wastewater lift stations
  • Comprehensive technical documentation (wiring diagrams, sensitivity curves, probe spacing guide)
  • Responsive customer service and support

Applications

  • Sump / sewage lift station pump control (pump-down / alternating twin-pump with external interlock)
  • Process tank fill control (pump-up — maintain level between Hi/Lo probes)
  • High / low level alarm annunciation (separate alarm probe + RM4/RM22 in alarm-only mode)
  • Well / cistern level monitoring
  • Retrofit of older level switches with modern conductive probe system

Reviews

There are no reviews yet.

Be the first to review “Schneider Electric Harmony RM22LA32MR / RM4LA32B / RM4LA32F / RM4LA32M / RM4LA32MW — Liquid Level Control & Monitoring Relays”