SIEMENS QAM9120.040 Duct Temperature Sensor

SIEMENS QAM9120.040 Duct Temperature Sensor | Shop On Ebay

Factory New Parts : Warranty 12 Months​
Refurbished Units : Warranty 3-6 Months​
Tested & Certified | Ships Worldwide​
Technical / Configuration Support Available​
Warranty Extension and Urgent Delivery supported. Get your quote or lead time now !
分类: 标签:

描述

The SIEMENS QAM9120.040​ is a duct temperature sensor​ from Siemens Smart Infrastructure (Building Technologies division) . It features a 400 mm probe length​ (min. bending radius 10 mm) with a time constant of 30 seconds at 2 m/s airflow​ and dead time < 1 second​ . The sensor is housed in a polycarbonate base (RAL 7001 silver-grey)​ with a RAL 7016 cover​ and a PA 66 black mounting flange, weighing approximately 0.15 kg​ . With IP42 protection​ (IP54 achievable with optional cable gland) per EN 60529, Protection Class III​ per EN 60730-1, and an operating temperature range of -40°C to +70°C, this sensor is designed for reliable, long-term deployment in HVAC ductwork . It connects via screw terminals​ accommodating 1 × 2.5 mm² or 2 × 1.5 mm²​ wires, with an M16 × 1.5 cable entry gland​ for 5.5–7.2 mm diameter cables . The QAM9120.040 complies with EN 60730-1, carries CE marking, and is UL 873 listed​ .

Key Features

  • Duct temperature sensor​ for ventilation and air-conditioning systems
  • Probe length: 400 mm; minimum bending radius 10 mm
  • Time constant: 30 s at 2 m/s airflow; dead time < 1 s
  • Measurement accuracy: refer to Type Summary (per Siemens datasheet)
  • Housing: Polycarbonate base (RAL 7001 silver-grey) + RAL 7016 cover
  • Mounting flange: PA 66 (black)
  • Weight: approx. 0.15 kg
  • Protection degree: IP42 per EN 60529 (IP54 with optional cable gland)
  • Protection Class III​ per EN 60730-1
  • Electrical connection: Screw terminals for 1 × 2.5 mm² or 2 × 1.5 mm²
  • Cable entry: M16 × 1.5 gland for 5.5–7.2 mm diameter cables
  • Probe material: Copper with polyolefin insulation
  • Ambient operating temp: -40°C to +70°C; humidity 5–95% r.h. (IEC 60721-3-2 Class 3K5)
  • Transport/storage temp: -25°C to +70°C (IEC 60721-3-2 Class 2K3)
  • Standards & approvals: EN 60730-1, CE marking, UL 873
  • Dimensions: L1 max 400 mm × L2 min 97 mm × drilling Ø 37 mm
  • Country of Origin: Siemens Switzerland Ltd (Smart Infrastructure)

Technical Specifications

Parameter
Specification
Brand
Siemens Smart Infrastructure (Building Technologies)
Model
QAM9120.040
Product Type
Duct temperature sensor
Probe Length
400 mm
Min. Bending Radius
10 mm
Time Constant
30 s at 2 m/s airflow
Dead Time
< 1 s
Measuring Accuracy
Refer to Type Summary (per Siemens datasheet)
Housing Material
Polycarbonate base (RAL 7001 silver-grey); RAL 7016 cover
Mounting Flange
PA 66 (black)
Probe Material
Copper, polyolefin insulation
Weight
Approx. 0.15 kg
Protection Degree
IP42 per EN 60529 (IP54 with optional cable gland)
Protection Class
III per EN 60730-1
Power Supply
Passive sensor (no external power required)
Electrical Connection
Screw terminals for 1 × 2.5 mm² or 2 × 1.5 mm²
Cable Entry
M16 × 1.5 gland for 5.5–7.2 mm diameter cables
Operating Temperature
-40°C to +70°C; 5–95% r.h. (IEC 60721-3-2 Class 3K5)
Transport/Storage Temp.
-25°C to +70°C (IEC 60721-3-2 Class 2K3)
Mechanical Conditions
IEC 60721-3-3 Class 2M2
Standards
EN 60730-1 (Automatic electrical controls)
Approvals
CE marking, UL 873
Dimensions (L1 × L2 × Drilling)
400 mm (max) × 97 mm (min) × Ø 37 mm
Document Reference
Siemens Datasheet A6V12170203_en—_a, Edition 2021-01-06
Issued By
Siemens Switzerland Ltd, Smart Infrastructure Global Headquarters, Zug
Country of Origin
Switzerland / Germany (Siemens Smart Infrastructure)

Warranty & After-Sales

  • Factory new units: 12 months warranty
  • Refurbished units: 3-6 months warranty
  • Bench test: Visual inspection → probe integrity check (400 mm length, 10 mm min. bending radius verification) → resistance/continuity measurement → time constant verification (30 s @ 2 m/s) → IP42 enclosure test → screw terminal torque test → M16×1.5 cable gland fit test → -40°C and +70°C operational test
  • Technical support:
    • Model verification​ — confirming QAM9120.040 matches your HVAC application (duct air temperature measurement)
    • Controller compatibility​ — pairing with Siemens HVAC controllers (RWD, RL, RM, RD series) or third-party BACnet/DDC systems
    • Cable selection​ — recommending appropriate 2-wire cable (2 × 1.5 mm² or 1 × 2.5 mm²) for the M16×1.5 gland entry
    • Installation guidance​ — drilling template (Ø 37 mm hole), probe insertion depth (400 mm), bending radius precautions (≥10 mm)
    • Alternative model selection​ — if a different signal type or measurement range is needed, advising on QAM2120.040 (Ni1000, -50 to +80°C) or other QAM9xxx variants
    • BACnet / Modbus integration​ — connecting to building management systems via appropriate transmitters
  • Optional accessories: M16×1.5 cable gland (for IP54 upgrade), 2-wire shielded cable, duct mounting bracket, replacement polycarbonate cover
Delivery Time: 3-5 working days (standard) / Express available
⚠️ IMPORTANT — Read Before Ordering:
  1. The QAM9120.040 is a passive temperature sensor​ — it requires a compatible controller or transmitter with appropriate input (e.g., Ni1000, Pt1000, 0-10V, 4-20mA depending on variant) to generate a readable signal
  2. Verify your controller input type​ — Siemens QAM9xxx series includes variants with different sensing elements (refer to the complete Type Summary in the Siemens datasheet A6V12170203)
  3. Probe length is 400 mm​ — ensure your duct depth accommodates this; shorter (200mm) or longer (600mm) variants are available in the QAM9xxx family
  4. IP42 standard; IP54 only with optional cable gland — for high-humidity or washdown environments, specify the IP54 option
  5. Passive sensor​ — no power supply needed, but proper 2-wire cable routing away from power cables is essential to avoid interference
  6. For active output (0-10V or 4-20mA) variants, consider QAM2120.040​ (Ni1000, -50 to +80°C, 400mm probe) or consult the full Siemens QAM9xxx catalog
  7. Send us your HVAC controller model and duct dimensions — we’ll confirm the exact QAM9xxx variant for your application

Why Choose Our Store

  • Genuine Siemens Smart Infrastructure components​ — direct from authorized channels, no counterfeit risk
  • QAM9120.040 in stock​ — genuine Siemens Switzerland-manufactured duct temperature sensors
  • Full Siemens HVAC sensor portfolio​ — QAM9120.040, QAM2120.040, QAM2130.040, QAM2170.040, QAM2200.040, and related models
  • Siemens HVAC system expertise​ — we support RWD, RL, RM, RD controllers, BACnet/DDC integration, and complete building automation solutions
  • Comprehensive technical documentation​ — original Siemens datasheet A6V12170203, dimensional drawings, installation guides
  • Global supply network​ with competitive pricing
  • Responsive customer service​ — multilingual support team

Applications

  • Air handling units (AHU)​ — supply/return air temperature measurement for VAV and CAV systems
  • Duct temperature sensing​ — ventilation and air-conditioning systems
  • Supply/extract air temperature monitoring​ — HVAC control loops
  • Limit sensor applications​ — e.g., low supply air temperature cutoff
  • Reference sensor​ — room setpoint adjustment based on outdoor temperature function
  • Measurement & display​ — standalone temperature measurement for BMS dashboards
  • Building automation systems​ — integration with Siemens Desigo CC, APOGEE, and third-party BACnet/MODBUS BMS
  • Cleanrooms & laboratories​ — precise duct air temperature control
  • Horticulture / agricultural greenhouses​ — duct climate control (similar to QAM2120.040 applications)
  • Industrial ventilation​ — process air temperature monitoring in factories, warehouses, and plants

评价

目前还没有评价

成为第一个“SIEMENS QAM9120.040 Duct Temperature Sensor” 的评价者