SIEMENS QAM9120.040 Duct Temperature Sensor

SIEMENS QAM9120.040 Duct Temperature Sensor | Shop On Ebay

Factory New Parts : Warranty 12 Months​
Refurbished Units : Warranty 3-6 Months​
Tested & Certified | Ships Worldwide​
Technical / Configuration Support Available​
Warranty Extension and Urgent Delivery supported. Get your quote or lead time now !
分类: 标签:

描述

The SIEMENS QAM9120.040​ is a duct temperature sensor​ from Siemens Smart Infrastructure (Building Technologies division) . It features a 400 mm probe length​ (min. bending radius 10 mm) with a time constant of 30 seconds at 2 m/s airflow​ and dead time < 1 second​ . The sensor is housed in a polycarbonate base (RAL 7001 silver-grey)​ with a RAL 7016 cover​ and a PA 66 black mounting flange, weighing approximately 0.15 kg​ . With IP42 protection​ (IP54 achievable with optional cable gland) per EN 60529, Protection Class III​ per EN 60730-1, and an operating temperature range of -40°C to +70°C, this sensor is designed for reliable, long-term deployment in HVAC ductwork . It connects via screw terminals​ accommodating 1 × 2.5 mm² or 2 × 1.5 mm²​ wires, with an M16 × 1.5 cable entry gland​ for 5.5–7.2 mm diameter cables . The QAM9120.040 complies with EN 60730-1, carries CE marking, and is UL 873 listed​ .

Key Features

  • Duct temperature sensor​ for ventilation and air-conditioning systems
  • Probe length: 400 mm; minimum bending radius 10 mm
  • Time constant: 30 s at 2 m/s airflow; dead time < 1 s
  • Measurement accuracy: refer to Type Summary (per Siemens datasheet)
  • Housing: Polycarbonate base (RAL 7001 silver-grey) + RAL 7016 cover
  • Mounting flange: PA 66 (black)
  • Weight: approx. 0.15 kg
  • Protection degree: IP42 per EN 60529 (IP54 with optional cable gland)
  • Protection Class III​ per EN 60730-1
  • Electrical connection: Screw terminals for 1 × 2.5 mm² or 2 × 1.5 mm²
  • Cable entry: M16 × 1.5 gland for 5.5–7.2 mm diameter cables
  • Probe material: Copper with polyolefin insulation
  • Ambient operating temp: -40°C to +70°C; humidity 5–95% r.h. (IEC 60721-3-2 Class 3K5)
  • Transport/storage temp: -25°C to +70°C (IEC 60721-3-2 Class 2K3)
  • Standards & approvals: EN 60730-1, CE marking, UL 873
  • Dimensions: L1 max 400 mm × L2 min 97 mm × drilling Ø 37 mm
  • Country of Origin: Siemens Switzerland Ltd (Smart Infrastructure)

Technical Specifications

Parameter
Specification
Brand​
Siemens Smart Infrastructure (Building Technologies)
Model​
QAM9120.040
Product Type​
Duct temperature sensor
Probe Length​
400 mm
Min. Bending Radius​
10 mm
Time Constant​
30 s at 2 m/s airflow
Dead Time​
< 1 s
Measuring Accuracy​
Refer to Type Summary (per Siemens datasheet)
Housing Material​
Polycarbonate base (RAL 7001 silver-grey); RAL 7016 cover
Mounting Flange​
PA 66 (black)
Probe Material​
Copper, polyolefin insulation
Weight​
Approx. 0.15 kg
Protection Degree​
IP42 per EN 60529 (IP54 with optional cable gland)
Protection Class​
III per EN 60730-1
Power Supply​
Passive sensor (no external power required)
Electrical Connection​
Screw terminals for 1 × 2.5 mm² or 2 × 1.5 mm²
Cable Entry​
M16 × 1.5 gland for 5.5–7.2 mm diameter cables
Operating Temperature​
-40°C to +70°C; 5–95% r.h. (IEC 60721-3-2 Class 3K5)
Transport/Storage Temp.​
-25°C to +70°C (IEC 60721-3-2 Class 2K3)
Mechanical Conditions​
IEC 60721-3-3 Class 2M2
Standards​
EN 60730-1 (Automatic electrical controls)
Approvals​
CE marking, UL 873
Dimensions (L1 × L2 × Drilling)​
400 mm (max) × 97 mm (min) × Ø 37 mm
Document Reference​
Siemens Datasheet A6V12170203_en—_a, Edition 2021-01-06
Issued By​
Siemens Switzerland Ltd, Smart Infrastructure Global Headquarters, Zug
Country of Origin​
Switzerland / Germany (Siemens Smart Infrastructure)

Warranty & After-Sales

  • Factory new units: 12 months warranty
  • Refurbished units: 3-6 months warranty
  • Bench test: Visual inspection → probe integrity check (400 mm length, 10 mm min. bending radius verification) → resistance/continuity measurement → time constant verification (30 s @ 2 m/s) → IP42 enclosure test → screw terminal torque test → M16×1.5 cable gland fit test → -40°C and +70°C operational test
  • Technical support:
    • Model verification​ — confirming QAM9120.040 matches your HVAC application (duct air temperature measurement)
    • Controller compatibility​ — pairing with Siemens HVAC controllers (RWD, RL, RM, RD series) or third-party BACnet/DDC systems
    • Cable selection​ — recommending appropriate 2-wire cable (2 × 1.5 mm² or 1 × 2.5 mm²) for the M16×1.5 gland entry
    • Installation guidance​ — drilling template (Ø 37 mm hole), probe insertion depth (400 mm), bending radius precautions (≥10 mm)
    • Alternative model selection​ — if a different signal type or measurement range is needed, advising on QAM2120.040 (Ni1000, -50 to +80°C) or other QAM9xxx variants
    • BACnet / Modbus integration​ — connecting to building management systems via appropriate transmitters
  • Optional accessories: M16×1.5 cable gland (for IP54 upgrade), 2-wire shielded cable, duct mounting bracket, replacement polycarbonate cover
Delivery Time: 3-5 working days (standard) / Express available
⚠️ IMPORTANT — Read Before Ordering:
  1. The QAM9120.040 is a passive temperature sensor​ — it requires a compatible controller or transmitter with appropriate input (e.g., Ni1000, Pt1000, 0-10V, 4-20mA depending on variant) to generate a readable signal
  2. Verify your controller input type​ — Siemens QAM9xxx series includes variants with different sensing elements (refer to the complete Type Summary in the Siemens datasheet A6V12170203)
  3. Probe length is 400 mm​ — ensure your duct depth accommodates this; shorter (200mm) or longer (600mm) variants are available in the QAM9xxx family
  4. IP42 standard; IP54 only with optional cable gland — for high-humidity or washdown environments, specify the IP54 option
  5. Passive sensor​ — no power supply needed, but proper 2-wire cable routing away from power cables is essential to avoid interference
  6. For active output (0-10V or 4-20mA) variants, consider QAM2120.040​ (Ni1000, -50 to +80°C, 400mm probe) or consult the full Siemens QAM9xxx catalog
  7. Send us your HVAC controller model and duct dimensions — we’ll confirm the exact QAM9xxx variant for your application

Why Choose Our Store

  • Genuine Siemens Smart Infrastructure components​ — direct from authorized channels, no counterfeit risk
  • QAM9120.040 in stock​ — genuine Siemens Switzerland-manufactured duct temperature sensors
  • Full Siemens HVAC sensor portfolio​ — QAM9120.040, QAM2120.040, QAM2130.040, QAM2170.040, QAM2200.040, and related models
  • Siemens HVAC system expertise​ — we support RWD, RL, RM, RD controllers, BACnet/DDC integration, and complete building automation solutions
  • Comprehensive technical documentation​ — original Siemens datasheet A6V12170203, dimensional drawings, installation guides
  • Global supply network​ with competitive pricing
  • Responsive customer service​ — multilingual support team

Applications

  • Air handling units (AHU)​ — supply/return air temperature measurement for VAV and CAV systems
  • Duct temperature sensing​ — ventilation and air-conditioning systems
  • Supply/extract air temperature monitoring​ — HVAC control loops
  • Limit sensor applications​ — e.g., low supply air temperature cutoff
  • Reference sensor​ — room setpoint adjustment based on outdoor temperature function
  • Measurement & display​ — standalone temperature measurement for BMS dashboards
  • Building automation systems​ — integration with Siemens Desigo CC, APOGEE, and third-party BACnet/MODBUS BMS
  • Cleanrooms & laboratories​ — precise duct air temperature control
  • Horticulture / agricultural greenhouses​ — duct climate control (similar to QAM2120.040 applications)
  • Industrial ventilation​ — process air temperature monitoring in factories, warehouses, and plants

评价

目前还没有评价

成为第一个“SIEMENS QAM9120.040 Duct Temperature Sensor” 的评价者