Omron 61F-G3 Electrode Type Level Controller

Omron 61F-G3 Electrode Type Level Controller (for 61F-11/12 Relay Unit / Standalone 61F-GP Series) |  Shop On eBay

Factory New Parts : Warranty 12 Months​
Refurbished Units : Warranty 3-6 Months​
Tested & Certified | Ships Worldwide​
Technical / Configuration Support Available​
Warranty Extension and Urgent Delivery supported. Get your quote or lead time now !

Description

The Omron 61F-G3​ is an Electrode (Conductivity) Type Level Controller / Relay Unit​ from the classic 61F Series, designed to detect liquid levels (conductive liquids only — water, aqueous solutions) by measuring conductivity between a common electrode and high/low probe electrodes. The suffix “G3” typically denotes the Relay Main Unit (with or without built-in pump control logic depending on sub-suffix — G3 = 3-wire control: common(COM), high(H), low(L) electrodes; some G versions are for float-less / electrode control with pump alternating function).
  • 61F-G3​ → AC-powered (100–240V AC or 24V AC/DC depending on exact sub-code — standard 61F-G3 = 100–240V AC 50/60Hz input) — provides SPDT relay output (1 c/o — NO/NC) for alarm or pump control, and often a second SPDT for pump alternation / high-high alarm on -G4 versions; the G3 is the 3-electrode (Common + High + Low) single-pump / single-alarm version.
    Clarification:Omron 61F series naming: 61F-GP-N / 61F-GP-AC110/220 = standalone electrode controller with built-in relay; 61F-G3 often references the *relay base unit used with 61F-11N/-12N expansion or the GP version — in modern catalog 61F-G3 ≈ 61F-GP-N (General Purpose electrode controller, 3-electrode, 1 pump relay + 1 alarm relay on some -G3N versions — check your exact 20-char). The “Float Less” in your query = “Floatless Level Switch” — Omron’s term for conductivity-based level detection (no moving float).
  • The 61F-G3 works with electrode rods (61F-EC□□ / 61F-EZ□□ — sold separately)​ screwed into tank — connected via terminal block on 61F-G3: E (Common / Earth electrode immersed always), H (High-level electrode — when covered → pump OFF / alarm), L (Low-level electrode — when uncovered → pump ON / alarm). Sensitivity adjustable (5–50 kΩ typical) to accommodate different water purity (pure water = high resistance → may need lower sensitivity / different electrode spacing).
  • Typical use: Sump pump control (auto ON at Low probe / OFF at High probe), tank overfill / dry-run alarm, boiler drum level monitoring (conductive media only — NOT for oil / hydrocarbon / deionized water unless special low-sensitivity setting).

Key Features

  • Level Detection Method: Conductivity (Floatless — no moving parts / floats)
  • Electrode Inputs: 3-wire (Common E + High H + Low L — also test T terminal on some)
  • Control Output: 1 × SPDT relay (pump/valve control — rated 5A 250V AC resistive) + often 1 × SPDT alarm relay (on -G3N / GP-N — check sub-suffix)
  • Sensitivity Adjustment: 5–50 kΩ (turn potentiometer — set to ~2× the liquid resistance between E & H probes)
  • Power Supply: 100–240 V AC (50/60 Hz — typical for 61F-G3; 24V AC/DC version = 61F-G3-D or 61F-GP-D)
  • Country of Origin: Japan (Omron Corporation)

Model & Variant Reference (Omron 61F Floatless / Electrode Level Controllers)

Model
Power / Type
Electrode Inputs
Output
Notes
61F-G3​ (listed)
100–240V AC — Relay Unit (GP type)
3 (E/H/L) + Test T
1 SPDT pump + 1 SPDT alarm (on G3N/GP-N — verify suffix)
Classic “Floatless” conductivity controller — needs electrode rods (61F-EC8 / EZ8 etc.)
61F-G4
100–240V AC
3 + Alternating Pump Ctrl
2 × SPDT (pump A/B alternate) + alarm
Dual-pump alternating — lead-lag change each cycle
61F-GP-N / 61F-GP-AC110/220
Same as modern G3 — renamed GP series
3 (E/H/L)
1 × SPDT (5A) + 1 × SPDT alarm (some)
Modern equivalent — G3 often cross-ref to 61F-GP-N
61F-11N / 61F-12N
Expansion Relay Units (for multi-point alarm)
N/A (driven by 61F-G3)
Adds extra alarm relays
Used with G3 base for extra high/low alarms
61F-EC8 / 61F-EZ8
Electrode Rod (8″ / 200mm titanium/SS)
Sold separately — screws into tank, wires to 61F-G3 E/H/L terminals
⚠️ Critical Notes:
  1. Conductive Liquids Only!: 61F-G3 detects via electrical conductivity — works for water, wastewater, brine, beer, etc. Does NOT work for oil, pure distilled/deionized water (< ~1 µS/cm — too high resistance >50kΩ — may need special low-sensitivity unit or capacitance type), gasoline, non-aqueous solvents.​ For non-conductive → use 61F-CAP (capacitance) or ultrasonic/float.
  2. Electrodes Sold Separately: You need electrode rods (61F-EC□ / 61F-EZ□ — lengths 100/200/300mm etc.) + electrode holder (61F-HP□ / tank bushing)​ — wire from rod terminal → 61F-G3 terminals: E(Common always submerged), H(High — pump cutoff), L(Low — pump start). Test T = momentary test input (shorts E-H internally to simulate high level — checks relay trip).
  3. Sensitivity Setting: Measure resistance between E & H probes immersed in your liquid → set sensitivity pot to ~½ that value (or just below liquid resistance — unit trips when R < setpoint). Too high sensitivity → false trigger from moisture/condensation on leads; too low → miss shallow coverage.
  4. Wiring — Pump Control Logic: Typical pump-down (sump): L probe uncovered → pump ON; H probe covered → pump OFF. Reverse pump-up (fill tank): L uncovered → fill valve ON; H covered → fill valve OFF. 61F-G3 has built-in hysteresis & pump delay (adjustable on some — check if your G3 has “Delay Time” pot — typical 0–10 s).
  5. “Float Less” = Japanese/English marketing term: Omron calls their conductivity-based level switch “Floatless Level Switch / Controller” — no float = no mechanical wear. The 61F-G3 IS the “Floatless” controller — it replaces float switches with electrode probes.

Technical Specifications (61F-G3 — Electrode (Floatless) Level Controller, 100–240V AC, 3-Probe + Test)

Parameter
Specification
Model / Order Code
61F-G3 (Omron 61F Series Floatless Level Controller — Electrode Type)
Series
61F (classic conductivity level control — “Floatless”)
Power Supply
100–240 V AC (50/60 Hz) — some -D suffix = 24V AC/DC — verify full code
Electrode Inputs
3 + Test: E (Common — always immersed), H (High level), L (Low level), T (Test — momentarily shorts E-H to simulate high)
Sensitivity (Conductivity Setpoint)
Adjustable 5–50 kΩ (potentiometer on front — set < liquid resistance between E↔H/L)
Control Output — Pump/Main
1 × SPDT relay — 5 A 250 V AC resistive (NO/NC configurable — pump start/stop)
Alarm Output (on G3N / GP-N)
1 × SPDT relay — 5 A 250 V AC (high-high / dry-run / electrode fault — check suffix)
Pump Delay / Hysteresis
Typically 0–10 s adjustable (some versions fixed ~2 s) — prevents chatter near level
Indicators (LED)
PWR (green — supply OK), PUMP (yellow — pump relay energized), ALM (red — alarm if fitted)
Back-panel / Terminals
Screw terminals (M3.5 — accept AWG 24–14 / 0.2–2.5 mm²) for AC supply, E/H/L/T, relay contacts
Operating Temp.
-10 … +55 °C (no freezing/dewing)
Dimensions (W×H×D)
~ 45 mm(W) × 90 mm(H) × 100 mm(D) — DIN rail mount (35 mm top hat) or surface
Weight
~ 0.25 kg
Standards
CE, UL, cUL, KC, RoHS (newer lots)
Required Accessories (sold sep.)
Electrode rods (61F-EC8 / EZ8 / custom length), electrode holder / tank bushing (61F-HP□), wiring to tank
Country of Origin
Japan (Omron Corporation)

Warranty & After-Sales

  • Factory new units: 12 months warranty
  • Refurbished units: 3-6 months warranty (power-up + simulate probe wet/dry via test terminal → verify relay pick/drop)
  • Technical support for:
    • Electrode selection (61F-EC8 = 8″ Ti rod; EZ8 = 8″ SS rod — for mild/aggressive media; custom length avail 61F-EC□□ / EZ□□ up to 1m+)
    • Sensitivity setting walkthrough (measure R between E↔H in liquid → set pot slightly below that Ω value — e.g., liquid R=15kΩ → set ~10kΩ)
    • Pump logic wiring (sump: L=low probe → pump ON; H=high → pump OFF — wire pump contactor coil to NO/Common of pump relay; add overload in series)
    • Alarm usage (dry-run / overfill — if G3 has alarm relay, wire to announce probe failure or high-high)
    • Cross-ref to 61F-GP-N (modern GP series = functional equivalent to G3 in most apps)
    • Tank bushing / electrode holder (61F-HP3 / HP4 — Rp 1/2″ / 3/4″ PT or PF)
  • Optional: Electrode rods (61F-EC8 / EZ8 / EC15 / EZ15), holder (61F-HP3 / HP4), expansion alarm unit (61F-11N), 24V DC PSU if using DC version

Delivery Time

  • Standard delivery: 3-5 working days (stock NOS)
  • Express shipping available upon request

Why Choose Our Store

  • Genuine Omron 61F series — not aftermarket (sensitivity pot & relay contact rating critical for long life)
  • Global supply network with competitive pricing on legacy Omron level controls
  • Expertise in Omron 61F electrode level system (probe selection, sensitivity adj., pump logic wiring, cross to GP series)
  • Comprehensive technical documentation (61F-G3 terminal layout, electrode wiring diagram E/H/L, sensitivity set procedure, pump hookup sketch)
  • Responsive customer service and support

Applications

  • Sump / Sewage Pump Control: Auto ON at Low probe / OFF at High probe — 61F-G3 + electrode rods in pit.
  • Tank Overfill / Dry-Run Protection: High-level alarm (H probe covered → alarm relay) + Low-level (L uncovered → dry-run warn).
  • Boiler / Process Vessel (Conductive Media): Monitor conductive liquid level — stainless steel or Ti electrodes resist corrosion.
  • Retrofit Float Switches: Replace mechanical float (prone to stick/scale) with 61F electrodes — no moving parts.
  • Wastewater / Cooling Tower Basin: Reliable even with mildly dirty water (periodically clean electrodes of scale).